File transfer#
You can used FX-Editor to transfer files to substation. Protocol is SFTP so user can use also use external softwares to do file transfer.
Folder structure#
All permanent files are located in mass memory of type FlashDisk. It can be referenced using name HDisk Files used by Fx2020 substation software are in folder /hdisk/fidelix Folder /hdisk/fidelix/Bin contains Windows CE program modules of substation software Folder /hdisk/fidelix/Bin/htm contains programs used with browser. Folder /hdisk/fidelix/Data contains all programmed data of substation. - AlarmGroup.dat contains alam groups - IECPRG.dat contains IEC programs - Modules.dat contains information about I/O modules - Pointdata.dat contains point database - Settings.dat contains different settings - StateText.dat contains state text groups - UserData.dat contains user information Folder /hdisk/fidelix/www contains graphics files (htm files) Folder /hdisk/fidelix/sys contains system information, don’t touch them