DOOC-16-C#

16-Channel digital output module
../../_images/dooc16c1.png

Training video#

Technical features#

  • 16 closed or open loop input channels

  • 24 VDC power supply

  • DIN-rail mountable

  • Modbus server (formerly slave) module using RTU over RS485 @ 9600..57600 bps (autodectect speed), 8 databits, No Parity, 1 stop bit

  • Modbus address set from 1 to 63 using DIP-switches on the side of the module

  • Power supply (24 VDC) and communication (A/+ & B/-) via T-Bus connector clicked onto the DIN-rail

  • Each channel has a green LED, lighting up steadily when the output is active, blinking green when the output is active but too little current is used (less than 2.5 mA or the resistance is bigger than +/- 10 kΩ), and blinking red when the output is active but there is a short-circuit detected (resistance is < 240 Ω).

Connections#

Connections - Power supply and Communication Bus
../../_images/dooc16c2.png ../../_images/dooc16c3.jpg ../../_images/dooc16c4.jpg ../../_images/dooc16c5.jpg

Verify your skills:#

--- primary_color: orange secondary_color: lightgray text_color: black shuffle_questions: false --- ## Select the outputs you can connect to the DOOC-16-C Digital Output Module > Which ones are controlled ON/OFF by the FX-module? - [ ] Temperature measurement - [ ] Running indication of a fan - [x] Pump control On/Off - [x] Damper control close/open - [x] Alarm status for external alarm trasmitter - [x] Permission to start water cooling system ## What type of signal(s) can be connected to the DOOC-16-C module ? > Do you find that in the module? - [ ] Potential free output - [x] 24 VDC output with load between 2,5 to 100 mA current - [ ] 230 VAC output with load up to 1 A - [ ] 110 VAC output with load up to 1 A - [ ] change over / transfer contacts ## What type of power supply do the FdxCompact I/O-modules require ? > Do you find that in the module? - [x] 24 VDC - [ ] 24 VAC - [ ] 48 VDC - [ ] 230 VAC - [ ] 110 VAC

Recap:#

  • Check the datasheet to recap the major features: Datasheet